Instrumentation Cables 

   EN 50288-7 Instrumentation Cables
PE Insulated, LSZH Sheathed & Overall Screened Instrumentation Cables (Multipair)

RE-2Y(St)H 90°C / 300V

EN 50288-7 Instrumentation Cables

STANDARDS
Basic design to EN 50288-7

APPLICATION 
The unarmoured LSZH sheathed cables are generally use for indoor installation and suitable for wet and damp areas. Generally, the cables are used within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for the interconnection of electrical equipment and instruments, the LSZH sheath can reduce toxic smoke and fume emission. 

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); 
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation   (Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; 
CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; 
CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; 
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance ICEA S-73-532**

Note: Asterisk * denotes superseded standard, **Test temperature +60°C, duration 4h. Retention: min 60% of tensite strength/min.60% of elongation.

VOLTAGE RATING
300V 

CABLE CONSTRUCTION
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: PE compound, EN 50290. 2-23.
Pairs: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm
Binder tape: PETP transparent tape
Overall Screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type
 SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

COLOUR CODE
Insulation: Black / White, continuously numbered on white core(1, 2..)for multipair.
Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES
Temperature Range During Operation (Fixed State): -30°C – +90°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius:  7.
5 X Overall Diameter

CONSTRUCTION PARAMETERS

Caledonian Cable Code RE-2Y(St)H
No. of  Pairsx2 xCross  Section Nominal Insulation Thickness Nominal Outer Sheath Thickness Nominal Overall Diameter Approx.  Weight
No.x2xmm2 mm mm mm kg/km
0.5mm2, Multipair
RE-2Y(St)H 2P0.5 2x2x0.5 0.35 0.9 7.6 66
RE-2Y(St)H 4P0.5 4x2x0.5 0.35 0.9 8.8 98
RE-2Y(St)H 5P0.5 5x2x0.5 0.35 1.0 9.8 118
RE-2Y(St)H 6P0.5 6x2x0.5 0.35 1.0 10.6 138
RE-2Y(St)H 8P0.5 8x2x0.5 0.35 1.0 11.3 160
RE-2Y(St)H 10P0.5 10x2x0.5 0.35 1.1 12.9 201
RE-2Y(St)H 12P0.5 12x2x0.5 0.35 1.1 13.5 236
RE-2Y(St)H 16P0.5 16x2x0.5 0.35 1.1 15.2 300
RE-2Y(St)H 20P0.5 20x2x0.5 0.35 1.2 16.9 367
RE-2Y(St)H 24P0.5 24x2x0.5 0.35 1.2 18.3 419
0.75mm2, Multipair
RE-2Y(St)H 2P0.75 2x2x0.75 0.38 0.9 8.5 87
RE-2Y(St)H 4P0.75 3x2x0.75 0.38 1.0 10.0 123
RE-2Y(St)H 5P0.75 4x2x0.75 0.38 1.0 10.9 150
RE-2Y(St)H 6P0.75 5x2x0.75 0.38 1.0 11.8 175
RE-2Y(St)H 8P0.75 8x2x0.75 0.38 1.1 12.8 220
RE-2Y(St)H 10P0.75 10x2x0.75 0.38 1.1 14.5 267
RE-2Y(St)H 12P0.75 12x2x0.75 0.38 1.1 15.1 298
RE-2Y(St)H 16P0.75 16x2x0.75 0.38 1.2 17.3 409
RE-2Y(St)H 20P0.75 20x2x0.75 0.38 1.3 19.2 480
RE-2Y(St)H 24P0.75 24x2x0.75 0.38 1.3 20.8 561
1.0mm2, Multipair
RE-2Y(St)H 2P1.0 2x2x1.0 0.4 0.9 9.2 102
RE-2Y(St)H 4P1.0 3x2x1.0 0.4 1.0 10.9 156
RE-2Y(St)H 5P1.0 4x2x1.0 0.4 1.0 11.9 183
RE-2Y(St)H 6P1.0 5x2x1.0 0.4 1.0 13.0 224
RE-2Y(St)H 8P1.0 8x2x1.0 0.4 1.1 14.0 273
RE-2Y(St)H 10P1.0 10x2x1.0 0.4 1.1 15.9 324
RE-2Y(St)H 12P1.0 12x2x1.0 0.4 1.2 16.8 383
RE-2Y(St)H 16P1.0 16x2x1.0 0.4 1.2 19.0 513
RE-2Y(St)H 20P1.0 20x2x1.0 0.4 1.3 21.1 619
RE-2Y(St)H 24P1.0 24x2x1.0 0.4 1.4 23.1 738
1.3mm2, Multipair
RE-2Y(St)H 2P1.3 2x2x1.3 0.45 1.0 10.4 122
RE-2Y(St)H 4P1.3 3x2x1.3 0.45 1.0 12.0 190
RE-2Y(St)H 5P1.3 4x2x1.3 0.45 1.1 13.4 233
RE-2Y(St)H 6P1.3 5x2x1.3 0.45 1.1 14.6 273
RE-2Y(St)H 8P1.3 8x2x1.3 0.45 1.2 15.7 330
RE-2Y(St)H 10P1.3 10x2x1.3 0.45 1.2 17.9 422
RE-2Y(St)H 12P1.3 12x2x1.3 0.45 1.3 18.9 487
RE-2Y(St)H 16P1.3 16x2x1.3 0.45 1.3 21.4 678
RE-2Y(St)H 20P1.3 20x2x1.3 0.45 1.4 23.8 790
RE-2Y(St)H 24P1.3 24x2x1.3 0.45 1.5 25.9 921
1.5mm2, Multipair
RE-2Y(St)H 2P1.5 2x2x1.5 0.45 1.0 10.8 139
RE-2Y(St)H 4P1.5 3x2x1.5 0.45 1.1 12.7 212
RE-2Y(St)H 5P1.5 4x2x1.5 0.45 1.1 14.0 259
RE-2Y(St)H 6P1.5 5x2x1.5 0.45 1.2 15.2 312
RE-2Y(St)H 8P1.5 8x2x1.5 0.45 1.2 16.4 378
RE-2Y(St)H 10P1.5 10x2x1.5 0.45 1.3 18.8 473
RE-2Y(St)H 12P1.5 12x2x1.5 0.45 1.3 19.7 548
RE-2Y(St)H 16P1.5 16x2x1.5 0.45 1.4 22.5 727
RE-2Y(St)H 20P1.5 20x2x1.5 0.45 1.5 25.0 903
RE-2Y(St)H 24P1.5 24x2x1.5 0.45 1.5 27.1 1051

Note : Other conductor sizes & core configurations are available upon request

Electrical PROPERTIES

Conductor Area Size   mm 2   0.5  0.75   1.0   1.3 1.5  
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C)   Ω/km  36.7 25 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz)  pF/m(Max.)  
≤ 4 pairs 90 90 90 102 102
all other pairs 75 75 75 85 85
Capacitance unbalance(1 kHz)  pF/500 m (Max.) 500 
Inductance mH/km (Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage Urms V 300
Test Voltage  Core to Core  1500 
Core to Screen  1500